dc.contributor.author | Boobpa, Chatpong | en_US |
dc.contributor.author | ฉัตรพงษ์ บุบผา | en_US |
dc.date.accessioned | 2020-01-10T09:01:43Z | |
dc.date.available | 2020-01-10T09:01:43Z | |
dc.date.issued | 2020-01-10 | |
dc.identifier.uri | http://repository.rmutp.ac.th/handle/123456789/2936 | |
dc.description | วิทยานิพนธ์ (วศ.ม.) -- มหาวิทยาลัยเทคโนโลยีราชมงคลพระนคร, 2561 | en_US |
dc.description.abstract | To Improvement the power factor is very important. Because the costs are
increased or reduced. To Improvement the power factor, the higher the value, it is
necessary to buildings, offices and industrial buildings or the fact that the industry
needs real power. And reactive power source to operate.
This paper presents the design and construction of reactive power factor
control. Which amounted to 6 working order by the first sequence is divided into
three three-phase electrical power system and three consecutive singles phase by
active power different. first1 is reactive at 5 kVAr second 2 and third 3 are reactive at
2.5 kVAr forth 4, fifth 5 and sixth 6, precious marine active 0.83 kVAr control. the
power factor controller that controls RG3-12 pay Oval active in various sequences.
As a result, when not equipped with reactive power compensation software
to control the power factor. This makes the flow of the high and low Power Factor
schedule. When equipped compensate reactive power source to power factor
control. Single-phase motor 1 kW and light bulb 1,64-watt making the current
decline of 14 amps rest 12 amps of the power factor increases from 0.5 to 0.929.
When connected to three-phase motor with 2 kW 0.8,2.2 flow down from 2.360 rest
0.942 amps of power factor value up from 0.308 to 1.0. | en_US |
dc.description.sponsorship | Rajamangala University of Technology PhraNakhon | en_US |
dc.language.iso | th | en_US |
dc.subject | power factor | en_US |
dc.subject | power system | en_US |
dc.subject | reactive power | en_US |
dc.subject | ไฟฟ้า | eu_US |
dc.subject | ระบบไฟฟ้ากำลัง | eu_US |
dc.title | Power factor correction by reactive power control method | en_US |
dc.title.alternative | การปรับปรุงตัวประกอบกาลังด้วยวิธีการควบคุมกาลังไฟฟ้ารีแอคทีฟ | en_US |
dc.type | Thesis | en_US |
dc.contributor.emailauthor | chatpong.boobpa@hotmail.com | en_US |