This paper presents an assessment of the quality of electricity transmission and distribution system to supply power to the industrial area. The objective is to analyze the power quality that customer in the industrial area need high level. By analyzing the power quality of Provincial Electricity Authority (PEA) in transmission system 115 kV distribution system 22 kV and 400/230 volt in Rojana industrial park from power quality meters. The study concluded that the phenomenon occurs continuously consist of RMS voltage power frequency voltage unbalance short term flicker long term flicker Harmonic meet the standards applied to all. The phenomenon occurs temporary consist of transient voltage dip voltage swell interruption in the conclusion the power quality problems caused by voltage dip most, especially with loads which are sensitive to voltage. From the moment the measurement showed that the voltage dip on transmission system 115 kV maximum of 19 times. The voltage dip that occur including three voltage level of 30 times there are events that do not pass SEMI F47 standard 12 times or 40%.