Show simple item record

dc.contributor.authorPrakobkit, Surasiten_US
dc.contributor.authorสุรสิทธิ์ ประกอบกิจen_US
dc.date.accessioned2020-03-16T07:58:40Z
dc.date.available2020-03-16T07:58:40Z
dc.date.issued2020-03-16
dc.identifier.urihttp://repository.rmutp.ac.th/handle/123456789/3220
dc.descriptionรายงานวิจัย -- มหาวิทยาลัยเทคโนโลยีราชมงคลพระนคร, 2559en_US
dc.description.abstractElectricity Generating Authority of Thailand (EGAT) encountered problems voltage swell from the changes of power system configuration, high-voltage 115 kV substation name Lopburi2 to radial. Control Center closed capacitor bank caused the steel industry, electric power plants and renewable energy, solar tripped themselves out. As a result, EGAT loosed of power produced of solar power plants. It also affected confidence in the system's power consumption. EGAT’s necessary to learn from this event. This research was simulation power system modeling of “High Voltage Substation Lopburi2” and grid connection both the system EGAT and PEA with EMTDC-PSCAD for analysis of the voltage swell caused by close capacitor bank at “Lopburi2” substation compared with actual events, then calculated the voltage swell occurred at high voltage station linkage. Finally, this research presents a method of reduction of their impact of close capacitor bank at “Loburi2” to avoid the voltage swell in the future.en_US
dc.description.sponsorshipRajamangala University of Technology Phra Nakhonen_US
dc.language.isothen_US
dc.subjectOvervoltageen_US
dc.subjectแรงดันไฟฟ้าเกินen_US
dc.subjectElectromotive forceen_US
dc.subjectระบบส่งจ่ายไฟฟ้าen_US
dc.titleImpact assessment of voltage swell in transmission systemen_US
dc.title.alternativeการประเมินผลกระทบของแรงดันไฟฟ้าเกินในระบบส่งจ่ายไฟฟ้าen_US
dc.typeResearch Reporten_US
dc.contributor.emailauthorarit@rmutp.ac.then_US


Files in this item

Thumbnail

This item appears in the following Collection(s)

Show simple item record